SKU RT-BA300 Category

RPZ backflow preventer BA300

Two backflow preventers + drain valve

Data sheet

Product information

The BA300 is an RPZ valve to DIN EN 1717, developed to protect drinking water systems against backpressure, backflow and backsiphonage. It meets the requirements for liquid category 4 and is designed for use in residential construction, industry and commercial installations. The construction in powder-coated ductile iron and lead-free materials guarantees corrosion resistance, durability and easy maintenance.

Special features

  • Triple safety principle: two backflow preventers + drain valve
  • Liquid category 4 to DIN EN 1717
  • Bleifrei: < 0,1 % Bleigehalt aller Materialien
  • Powder-coated ductile iron body for increased corrosion protection
  • Standardised drain connection for easy integration
  • Zertifikate: DVGW, BELGAQUA, NF, KIWA, WRAS, SVGW, VdS
  • Optimierte Wartung: Schneller Zugriff auf interne Komponenten

Advantages

  • Three pressure zones formed by two backflow preventers and one drain valve
  • Approved for liquid category 4
  • Powder-coated ductile iron body
  • Approvals from DVGW, KIWA, WRAS, SVGW and VdS

Versions

  • Sizes: DN65, DN80, DN100, DN150, DN200
  • Standard version: flange connection PN10
  • Option: VdS-zertifizierte Version (BA300-80ZVDS)

Areas of application

  • Protection of the drinking water supply to DIN EN 1717
  • Liquid category 4 in conjunction with DIN 1988-100
  • Flanged lines DN 65 to DN 200 in PN 10
  • Plants with a standardised drain connection

Selection and installation

The BA300 covers liquid category 4 and is therefore the design for the highest hazard level in a drinking water installation. The drain connection must discharge freely – this must be taken into account when choosing the installation location.

FeatureValue
Nominal pressurePN 10
ConnectionDN 65 –
DN 200
Max. operating pressure10 bar
Min. Inlet pressure1.5 bar
Temperature rangeto 65 °C
(WRAS: 60 °C)
Body materialductile iron, powder-coated
SealsEPDM
Special featureDreifache safety, lead-free

Why backflow preventers or RPZ valves are indispensable

RPZ valves such as the BA300 are essential for safeguarding drinking water systems. They reliably prevent the backpressure, backflow and backsiphonage of contaminated media into the supply network. This is not only a technical necessity, but also a legal requirement in accordance with DIN EN 1717 and DIN 1988-100 in order to ensure hygiene and safety in water installations.

The triple safety architecture – consisting of two backflow preventers and a drain valve – divides the RPZ valve into three pressure zones. This completely eliminates the risk of contamination, even in the event of pressure fluctuations or malfunctions. For operators, this means: maximum operational safety, standard-compliant design and minimized liability risk.

Integration in SKID systems

We not only supply backflow preventers as individual components, but also integrate them into modular SKID systems. These preconfigured system solutions combine valves, piping, measurement and control technology into compact, ready-to-install units.

Typical areas of application for SKID systems with RPZ valves:

  • Chemical and pharmaceutical processes
  • Energy and power plants
  • Water treatment and food industry

This gives you a solution that combines safety, efficiency and flexibility – ideal for projects with high hygiene and process control requirements.

Fittings factory Fittings Ball valve Globe valve Pressure regulating valves Flow meter SKID Process plant Condensate trap Pump, compensators, backflow preventers, RPZ valves

FAQs

Which standard does the BA300 meet?

DIN EN 1717 for liquid category 4.

DN65 to DN200, flanged connection PN10.

Two non-return valves and a drain valve divide the separator into three pressure zones.

DVGW, BELGAQUA, NF, KIWA, WRAS, SVGW, VdS.

Optimized design for quick access to all components.

Insulation – In combination with valves and containers

Our insulations are more than just accessories – they perfectly complement valves and systems and increase efficiency, safety and adaptability.
Order and configure now.

We offer:

  • Custom-made insulating pads to fit your valves
  • Heating jacket integration – reliable even under extreme conditions
  • Insulation jackets and pipe insulation for SKID assemblies – ideal for modular systems and complex systems
  • Special solutions for high temperatures – for power plants, the chemical and process industries
Armaturenfabrik Valve insulation High-temperature pipe insulation with IFS-Plast25 insulation pads and IFS-MW20 mineral wool for SKID systems, process plants

Make a request directly

Would you like individual advice?

Benefit from our expert knowledge in process monitoring. Our experienced team will provide you with sound advice on selecting the optimum products for your specific requirements. Arrange your personal consultation now!
Cookie Consent with Real Cookie Banner